2 Parameters
2.2 List of parameters
SINAMICS G130/G150
534 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the minimum value for the motorized potentiometer of the technology controller.
Dependency: Refer to: p2237
Description: Sets the starting value for the motorized potentiometer of the technology controller.
For p2230.0 = 0, this setpoint is entered after ON.
Dependency: Refer to: p2230
Description: Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator of the technology
controller.
Dependency: Refer to: r2250
Description: Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency: Refer to: p2248
Note: The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-up is correspondingly extended.
p2238[0...n] Technology controller motorized potentiometer minimum value / Tec_ctrl mop min
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7954
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]
p2240[0...n] Technology controller motorized potentiometer starting value / Tec_ctrl mop start
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7954
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]
r2245 CO: Technology controller mot. potentiometer setpoint before RFG /
Tec_ctr mop befRFG
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7954
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p2247[0...n] Technology controller motorized potentiometer ramp-up time / Tec_ctr mop t_r-up
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7954
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [s] 1000.0 [s] 10.0 [s]

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals