EasyManuals Logo
Home>Siemens>Media Converter>SINAMICS G150

Siemens SINAMICS G150 User Manual

Siemens SINAMICS G150
1842 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #48 background imageLoading...
Page #48 background image
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
48 List Manual (LH2), 04/2014, A5E03263479A
Description: Displays the smoothed actual value of the DC link voltage.
Dependency: Refer to: r0070
Notice: This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
Note: A_INF, B_INF, S_INF: smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
Description: Displays the smoothed actual value of the DC link voltage.
Dependency: Refer to: r0070
Notice: For SINAMICS S120 AC Drive (AC/AC) the following applies:
When measuring a DC link voltage < 200 V, for the Power Module (e.g. PM340) a valid measured value is not
supplied. In this case, when an external 24 V power supply is connected, a value of approx. 24 V is displayed in the
display parameter.
Note: SERVO, VECTOR: Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
Description: Displays the smoothed absolute actual current value.
Dependency: Refer to: r0068
Notice: This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
For Basic Line Modules of chassis format, the displayed value is invalid as these units do not have any current
sensing.
Note: Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The absolute current actual value is available smoothed (r0027) and unsmoothed (r0068).
r0026 CO: DC link voltage smoothed / Vdc smooth
B_INF Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 5730, 6799,
8750, 8850, 8950
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r0026 CO: DC link voltage smoothed / Vdc smooth
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6799, 8750,
8850, 8950
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r0027 CO: Absolute actual current smoothed / I_act abs val smth
B_INF Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8750
P-Group: Displays, signals Units group: 6_4 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]

Table of Contents

Other manuals for Siemens SINAMICS G150