SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
853
2 Parameters
2.2 List of parameters
Description: Sets the transition time from STOP C to "Safe Operating Stop" (SOS).
Dependency: Refer to: p9552
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
SOS: Safe Operating Stop
Description: Sets the transition time from STOP D to "Safe Operating Stop" (SOS).
Dependency: Refer to: p9553
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
SOS: Safe Operating Stop
Description: Sets the transition time from STOP E to "Safe Operating Stop" (SOS).
Dependency: Refer to: p9554
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
SOS: Safe Operating Stop
Description: Sets the transition time from STOP F to STOP B.
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
p9352 SI Motion transition time STOP C to SOS (Motor Module) / SI Mtn t C->SOS MM
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2819
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [µs] 600000000.00 [µs] 100000.00 [µs]
p9353 SI Motion transition time STOP D to SOS (Motor Module) / SI Mtn t D->SOS MM
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2819
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [µs] 600000000.00 [µs] 100000.00 [µs]
p9354 SI Motion transition time STOP E to SOS (Motor Module) / SI Mtn t E->SOS MM
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [µs] 600000000.00 [µs] 100000.00 [µs]
p9355 SI Motion transition time STOP F to STOP B (Motor Module) / SI Mtn t F->B MM
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2819
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [µs] 600000000.00 [µs] 0.00 [µs]

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals