SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
567
2 Parameters
2.2 List of parameters
This parameter specifies the speed (n) of point 5 as a [%].
Dependency: Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3328
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: Displays the internal status of the infeed module.
Value: 0: Initialization
1: Fault
2: No ON command
3: Offset measurement running
4: ON delay active
5: Precharg. running
6: Operation
Description: Display and connector output for the status word of the infeed.
Description: Display and connector output for the status word of the DC link voltage control.
Note: Re bit 01:
DC-link voltage control is disabled and enabled with p3513.
Re bit 08 = 1:
DC-link voltage control is selected using p3513.
r3402 Infeed status internal BIC / INF state int
B_INF Can be changed: - Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 8932
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 6 -
r3405.7 CO/BO: Infeed status word / Inf ZSW
B_INF Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
07 DC link undervoltage alarm threshold
undershot
Yes No -
r3405.1...8 CO/BO: Status word DC link control / ZSW Vdc_ctrl
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
01 Vdc-ctrl active Yes No -
08 Vdc controller selected Yes No -