SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
427
2 Parameters
2.2 List of parameters
Description: Sets the integral time for the Lh adaptation of the motor model for an induction motor (ASM).
Description: Displays the corrective value for the Lh adaptation of the motor model for an induction motor (ASM).
Dependency: Refer to: p0826, p1780
Note: The adaptation result is reset if the magnetizing inductance of the induction motor is changed (p0360, r0382). This
also happens when changing over the data set if a different motor is not being used (p0826).
The display of the inactive data sets is only updated when changing over the data set.
Description: Displays the power-on stator frequency/ primary section frequency for the Lh adaptation for the induction motor
(ASM).
Description: Displays the power-on slip frequency for the Lh adaptation for the induction motor (ASM).
Description: Sets the integral time of the kT adaptation of the motor model for a permanent-magnet synchronous motor (PEM).
p1786[0...n] Motor model Lh adaptation integral time / MotMod Lh Tn
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
10 [ms] 10000 [ms] 100 [ms]
r1787[0...n] Motor model Lh adaptation corrective value / MotMod Lh corr
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
- [mH] - [mH] - [mH]
r1791 Motor model Lh adaptation power-on frequency / MotMod Lh f_on
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
- [Hz] - [Hz] - [Hz]
r1792 Motor model Lh adaptation power-on slip / MotMod Lh fslip
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
- [Hz] - [Hz] - [Hz]
p1795[0...n] Motor model kT adaptation integral time / MotMod kT Tn
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6731
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
10 [ms] 10000 [ms] 100 [ms]

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals