SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
695
2 Parameters
2.2 List of parameters
Description: Display and binector output for the state display PROFIenergy energy saving active or inactive.
Note: Bit 0 and bit 1 are inverse of one another.
Pe: PROFIenergy profiles
Description: Sets the signal source to set in the PROFIdrive state S1 "switching-on inhibit".
Dependency: Refer to: r5613
Note: Pe: PROFIenergy profiles
Description: Sets the phase shift of the second system with respect to the first system for the motor module for a 12-pulse gating
unit.
Value: 0: Shift by +30 °
1: Shift by -30 °
2: Shift by 0 °
3: Shift by +90 °
4: Shift by -90 °
5: Shift by +120 °
6: Shift by -120 °
7: Shift by +150 °
8: Shift by -150 °
Dependency: Refer to: p7003
Notice: The parameter is only evaluated if p7003 = 2.
Note: For p6397 = 0 the following applies: The second systems leads for a positive direction of rotation.
For p6397 = 1 the following applies: The second systems lags for a positive direction of rotation.
r5613.0...1 CO/BO: Pe energy-saving active/inactive / Pe save act/inact
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Pe active Yes No -
01 Pe inactive Yes No -
p5614 BI: Pe set switch-on inhibit signal source / Pe sw on_inh s_src
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p6397 Motor module phase shift second system / MM ph_sh 2nd sys
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 8 0