2 Parameters
2.2 List of parameters
SINAMICS G130/G150
342 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the delay time for the signal "braking threshold exceeded" (BO: r1229.6).
Dependency: Refer to: p1220, p1221, r1229
Description: Sets the brake control type (with or without diagnostics evaluation).
Example for brake control with diagnostics evaluation.
- brake control in the Motor Modules in booksize format
- Safe Brake Relay for AC Drive
Example for brake control without diagnostics evaluation.
- Brake Relay for AC Drive
Value: 0: Brake control with diagnostics evaluation
1: Brake control without diagnostics evaluation
Note: If the configuration of the motor holding brake (p1215) is set to "no holding brake present" when booting, then an
automatic identification of the motor holding brake will be carried out. If a brake control is detected without
diagnostics evaluation (e.g. Brake Relay for AC Drive), then the parameter is set to "brake control without diagnostics
evaluation".
It is not permissible to parameterize "brake control without diagnostics evaluation" and also enable "safe brake
control" (p1278 = 1, p9602 = 1, p9802 = 1).
Description: Sets the signal source for the OR/AND logic operation.
Dependency: Refer to: r1229
Note: [0]: OR logic operation, input 1 --> the result is displayed in r1229.10.
[1]: OR logic operation, input 2 --> the result is displayed in r1229.10.
[2]: AND logic operation, input 1 --> the result is displayed in r1229.11.
[3]: AND logic operation, input 2 --> the result is displayed in r1229.11.
p1277 Motor holding brake braking threshold delay exceeded / Del thresh exceed
VECTOR_G (Ext
brake)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2707
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 300.000 [s] 0.000 [s]
p1278 Brake control diagnostics evaluation / Brake diagnostics
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p1279[0...3] BI: Motor holding brake OR/AND logic operation / Brake OR AND
VECTOR_G (Ext
brake)
Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2707
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals