2 Parameters
2.2 List of parameters
SINAMICS G130/G150
642 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the mode to reset the actual value in XIST_ERW (CO: r4653).
Value: 0: Inactive
1: Reset with zero mark
2: Reset with BICO
3: Reset with selected zero mark
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency: Refer to: r4653, r4654, p4655
Note: If value = 1:
The value in XIST1_ERW is reset when passing every zero mark.
If value = 2:
The value in XIST1_ERW is reset with a 0/1 edge via binector input p4655.
If value = 3:
The value in XIST1_ERW is reset after a 0/1 edge via binector input p4655 when passing the next zero mark.
Description: Display and connector output for the actual value XIST1_ERW.
Dependency: Refer to: p4652, r4654, p4655
Description: Display and connector output for the actual value XIST1_ERW.
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency: Refer to: p4652, r4654, p4655
p4652[0...2] XIST1_ERW reset mode / XIST1_ERW res mode
VECTOR_G Can be changed: C1(3) Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 4750
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0
r4653 CO: XIST1_ERW actual value / XIST1_ERW actval
ENC Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 4750
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r4653[0...2] CO: XIST1_ERW actual value / XIST1_ERW actval
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 4750
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -