EasyManuals Logo
Home>Siemens>Media Converter>SINAMICS G150

Siemens SINAMICS G150 User Manual

Siemens SINAMICS G150
1842 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #837 background imageLoading...
Page #837 background image
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
837
2 Parameters
2.2 List of parameters
Description: Sets the monitoring clock cycle for safe motion monitoring.
Dependency: Refer to: p9500, p9511
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The monitoring clock cycle must be a multiple of the actual value sensing clock cycle in p9311 or of the DP clock
cycle.
A change only becomes effective after a POWER ON.
Description: Sets the enable signals for the safe motion monitoring.
Dependency: Refer to: p9501
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: A change only becomes effective after a POWER ON.
SDI: Safe Direction (safe motion direction)
SLP: Safely-Limited Position
SLS: Safely-Limited Speed
SOS: Safe Operating Stop
SP: Safe Position
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Description: Sets the axis type (linear axis or rotary axis/spindle).
Value: 0: Linear axis
1: Rot axis/spindle
p9300 SI Motion monitoring clock cycle (Motor Module) / SI Mtn clock MM
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
500.00 [µs] 25000.00 [µs] 12000.00 [µs]
p9301 SI Motion enable safety functions (Motor Module) / SI Mtn enable MM
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 0000
0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Enable SOS/SLS Enable Inhibit -
01 Enable SLP Enable Inhibit -
02 Enable absolute position Enable Inhibit -
03 Enable actual value synchronization Enable Inhibit -
16 Enable SSM hysteresis and filtering Enable Inhibit 2823
17 Enable SDI Enable Inhibit 2824
24 Enable transfer SLS limit value via
PROFIsafe
Enable Inhibit -
25 Enable transfer safe position via PROFIsafe Enable Inhibit -
26 Enable safe gearbox switchover Enable Inhibit -
27 Enable referencing via SCC Enable Inhibit -
p9302 SI Motion axis type (Motor Module) / SI Mtn AxisType MM
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals