2 Parameters
2.2 List of parameters
SINAMICS G130/G150
508 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the signal source for external alarm 3.
Note: An external alarm is triggered with a 1/0 signal.
Description: Sets the signal source for external alarm 3.
Note: An external alarm is triggered with a 1/0 signal.
Description: Selects faults or alarms for which the message type should be changed.
Dependency: Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2119
Note: Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
Description: Sets the message type for the selected fault or alarm.
Value: 1: Fault (F)
2: Alarm (A)
3: No message (N)
Dependency: Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2118
Note: Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
The message type can only be changed for messages with the appropriate identification (exception, value = 0).
Example:
F12345(A) --> Fault F12345 can be changed to alarm A12345.
In this case, the message number that may be possibly entered in p2100[0...19] and p2126[0...19] is automatically
removed.
p2117[0...n] BI: External alarm 3 / External alarm 3
B_INF, VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 2546
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p2117 BI: External alarm 3 / External alarm 3
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN, ENC,
HUB, TB30, TM150,
TM31, TM54F_MA,
TM54F_SL
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p2118[0...19] Change message type message number / Chng type msg_no
All objects Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: 8050, 8075
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0
p2119[0...19] Change message type type / Change type type
All objects Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 8050, 8075
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 3 1