SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
175
2 Parameters
2.2 List of parameters
Description: Sets the Sensor Module configuration.
Dependency: Refer to: p0437, p0600, p0601
Note: A value of zero is displayed if an encoder is not present.
Re bit 11:
When the property is set, the following parameters can be changed without the actual value in the encoder interface
becoming invalid (state r0481.14 = 1 "parking encoder active"):
p0314, p0315, p0430, p0431, p0441, p0442, p0443, p0444, p0445
Re bit 12:
The extended functions can be configured using p0437.
Re bit 13:
Encoder faults can be acknowledged via Gn_STW.15.
r0458 Sensor Module properties / SM properties
ENC Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 4704
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Encoder data available Yes No -
01 Motor data available Yes No -
02 Temperature sensor connection available Yes No -
03 Connection for PTC for motor with DRIVE-
CLiQ also available
Yes No -
04 Module temperature available Yes No -
05 Absolute encoder p0408/p0421 no power of
2
Yes No -
06 Sensor Module permits parking/unparking Yes No -
07 Hall sensor can be combined with actual
value inversion
Yes No -
08 Evaluation through several temperature
channels possible
Yes No -
09 Encoder fault and its associated information
available
Yes No -
10 Speed diagnostics in the Sensor Module Yes No -
11 Configuring without park state possible Yes No -
12 Extended functions available Yes No -
13 Extended encoder fault handling Yes No -
14 Extended singleturn/multiturn information
available
Yes No -
15 Evaluation function reserve Yes No -
16 Pole position identification Yes No -
17 Burst oversampling Yes No -
18 Continuous oversampling Yes No -
19 Safety position actual value sensing Yes No -
20 Extended speed calculation being used
(only SMC30)
Yes No -
21 Zero mark tolerance Yes No -
22 Rot pos adapt Yes No -
23 Commutation with zero mark can be de-
selected
Yes No -
24 Commutation with selected zero mark Yes No -
25 Disconnection of encoder power supply on
parking supported
Yes No -
26 Parking with temperature evaluation Yes No -
27 SSI position value extrapolation Yes No -
28 Cubic correction Yes No -
29 Phase correction Yes No -
30 Amplitude correction Yes No -
31 Offset correction Yes No -

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals