SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
89
2 Parameters
2.2 List of parameters
Description: Sets the number of Motor Data Sets (MDS).
Description: The motor data set is assigned to a motor using this parameter.
This unique component number is assigned when parameterizing the topology.
Only component numbers can be entered into this parameter that correspond to a motor.
Description: Configuration of the motor when commissioning the motor.
Dependency: For standard induction motors (p0301 > 10000), bit 0 is automatically preassigned the connection type of the
selected data set.
For p0100 > 0 (60 Hz rated motor frequency), it is not possible to select bit 1.
Refer to: p0304, p0305
Note: Re bit 00:
When changing the bits, the rated motor voltage p0304 and the rated motor current p0305 are automatically
converted to the selected connection type (star/delta).
For instance, this can be necessary if an 1LE1 motor is selected using the order number (MLFB) or code number
(p0300 = 100, p0301 = 1x0xx), and the motor connection type does not correspond to that of the data set.
Description: Copying a Motor Data Set (MDS) into another.
Index: [0] = Source motor data set
[1] = Target motor data set
[2] = Start copying procedure
p0130 Number of Motor Data Sets (MDS) / MDS count
VECTOR_G Can be changed: C1(3) Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: 8575
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 16 1
p0131[0...n] Motor component number / Mot comp_no
VECTOR_G Can be changed: C1(4) Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 199 0
p0133[0...n] Motor configuration / Motor config
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor connection type Delta Star -
p0139[0...2] Copy Motor Data Set MDS / Copy MDS
VECTOR_G Can be changed: C2(15) Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: 8575
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 31 0

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals