2 Parameters
2.1 Overview of parameters
SINAMICS G130/G150
18 List Manual (LH2), 04/2014, A5E03263479A
BICO: Full parameter name / abbreviated name
The following abbreviations can appear in front of the parameter name:
Drive object (function module)
A drive object (DO) is an independent, "self-contained" functional unit that has its own
parameters and, in some cases, faults and alarms.
When carrying out commissioning using the commissioning software, you can select/deselect
additional functions and their parameters by activating/deactivating function modules
accordingly.
The parameter list specifies the associated drive object and function module for each individual
parameter.
Examples:
• p1070 CI: Main setpoint
VECTOR
The parameter is only available with the VECTOR drive object, regardless of which function
modules have been activated.
• p1055 BI: Jog bit 0
VECTOR
The parameter is available with the VECTOR drive object, regardless of which function
modules have been activated (i.e. it is available with every activated function module
belonging to the drive object).
Note
The parameter list can contain parameters that are not visible in the expert lists of the particular
commissioning software (e.g. parameters for trace functions).
• BI: Binector Input
This parameter is used for selecting the source of a digital signal.
• BO: Binector output
This parameter is available as a digital signal for interconnection with other
parameters.
• CI: Connector Input
This parameter is used for selecting the source of an "analog" signal.
• CO: Connector output
This parameter is available as an "analog" signal for interconnection with other
parameters.
• CO/BO: Connector/Binector Output
This parameter is available as an "analog" and digital signal for interconnection
with other parameters.
Note
A connector input (CI) cannot be just interconnected with any connector output (CO, signal
source).
When interconnecting a connector input using the commissioning software, only the
corresponding possible signal sources are listed.