Description: Setting to reset the display in r0039 and r0041.
Procedure:
Set p0040 = 0 --> 1
The displays are reset and the parameter is automatically set to zero.
Dependency: Refer to: r0039
Description: Displays the saved energy referred to 100 operating hours.
Dependency: Refer to: p0040
Note: This display is used for a fluid-flow machine.
The flow characteristic is entered into p3320 ... p3329.
For an operating time of below 100 hours, the display is interpolated up to 100 hours.
Description: Sets the smoothing time constant for the following display values:
SERVO: r0078[1], r0079[1], r0081 (calculated from the quantities smoothed with p0045), r0082[1].
VECTOR: r0063[1], r0068[1], r0080[1], r0082[1].
Description: Display and BICO output for missing enable signals that are preventing the closed-loop infeed control from being
commissioned.
p0040 Reset energy consumption display / Energy usage reset
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
r0041 Energy consumption saved / Energy cons saved
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [kWh] - [kWh] - [kWh]
p0045 Display values smoothing time constant / Disp_val T_smooth
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 4715, 5610,
5730, 6714, 8012
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [ms] 10000.00 [ms] 1.00 [ms]
r0046.0...29 CO/BO: Missing enable sig / Missing enable sig
B_INF Can be changed: - Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: 8734
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 OFF1 enable missing Yes No -
01 OFF2 enable missing Yes No -
08 EP terminals enable missing Yes No -
16 OFF1 enable internal missing Yes No -
17 OFF2 enable internal missing Yes No -