2 Parameters
2.2 List of parameters
SINAMICS G130/G150
418 List Manual (LH2), 04/2014, A5E03263479A
As an alternative to a warm restart: save the parameters and carry out a POWER ON (switch-off/switch-on).
When the function "safety without encoder" (p9306/p9506) is activated, this setting is not permissible and results in
monitoring errors.
Re bit 6 = 1:
The following applies for encoderless vector control of induction motors:
For a blocked motor (see p2175, p2177) the time condition in p1758 is bypassed and a change is not made into
open-loop controlled operation.
The following applies for encoderless vector control of synchronous motors:
For a blocked motor (see p2175, p2177), the speed ramp-function generator is held in open-loop speed controlled
operation, and a change is not made into closed-loop controlled operation.
Re bit 7 = 1:
The following applies for encoderless vector control of induction motors:
If the changeover limits are parameterized too low (p1755, p1756), then they are automatically increased to rugged
values by the absolute amount p1749 * p1755.
The effective time condition for changing over into open-controlled operation is obtained from the minimum of p1758
and 0.5 * r0384.
Activation can make sense for applications that demand a high torque at low frequencies and therefore low speed
gradients.
Adequate parameterization must be ensured (p1610, p1611).
Description: Displays the status of the motor model.
Note: Re bit 17:
Displays the status when enabling the rugged model feedback (p1784) for operation with and without encoder.
The feedback is used to increase the parameter ruggedness of the motor model and is effective in the operating
range of the two-component closed loop current control.
r1751 Motor model status / MotMod status
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Controlled operation Active Inactive 6721
01 Set ramp-function generator Active Inactive -
02 Stop RsLh adaptation Yes No -
03 Feedback Active Inactive -
04 Encoder operation Active Inactive -
05 Holding angle Yes No -
06 Acceleration criterion Active Inactive -
07 Set angular integrator PEM Yes No -
08 Stop Kt adaptation PEM Yes No -
09 PolID active PEM sensorless Yes No -
10 I injection PEM Yes No -
11 Speed controller output cannot be set to
zero
Yes No -
12 Rs adapt waits Yes No -
13 Motor operation Yes No -
14 Stator frequency sign Positive Negative -
15 Torque sign Motor mode Regenerative mode -
16 Pulse injection active PEM Yes No -
17 Operation with rugged model feedback Enabled Inhibited -
18 Operation of the current model with current
feedback
Enabled Inhibited -
19 Current feedback in the current model Active Inactive -
20 Rugged increase of the changeover limits Active Inactive -
21 Motor blocked (RFG stop) PEM No Yes -