SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
401
2 Parameters
2.2 List of parameters
Description: Displays the calculated excitation current setpoint.
Dependency: Refer to: p0390
Description: Displays the load angle of the current model.
Description: Sets the dynamic response factor for the current model controller.
Description: Sets the proportional gain for the current model controller.
This value is automatically pre-set using p3900 or p0340 when commissioning has been completed.
Description: Sets the integral time for the current model controller.
This value is automatically pre-set using p3900 or p0340 when commissioning has been completed.
r1626 CO: Excitation current setpoint / I_exc_setp
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6727
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r1627 CO: Current model load angle / I_mod load angle
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6727
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: p2005 Expert list: 1
Min Max Factory setting
- [°] - [°] - [°]
p1628[0...n] Current model controller dynamic factor / I_mod_ctr dyn_fact
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6727
P-Group: Functions Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
1 [%] 400 [%] 50 [%]
p1629[0...n] Current model controller P gain / I_mod_ctrl Kp
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.000 100000.000 0.000
p1630[0...n] Current model controller integral time / I_mod_ctrl Tn
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [ms] 10000.00 [ms] 0.00 [ms]