2 Parameters
2.2 List of parameters
SINAMICS G130/G150
570 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the scaling factor for the power pre-control.
Dependency: Refer to: p3520
Note: The scaling factor acts on the sum of the associated indices of p3519 and p3520. As one BICO input is scaled
(p3519) and the other is not scaled (p3520), for each index, only one of the two inputs should be assigned.
Description: Displays the resulting smoothed linearized torque-generating pre-control current.
Dependency: Refer to: p3520, p3521, p3523
Note: These displays are used to set the correct scaling for the pre-control.
[0]:(p3519[0] + p3520[0]) * p3521[0] / r0070
[1]:(p3519[1] + p3520[1]) * p3521[1] / r0070
[2]:(p3519[2] + p3520[2]) * p3521[2] / r0070
[3]:(p3519[3] + p3520[3]) * p3521[3] / r0070
[4]: Total [0] ... [3]
Description: Sets the filter time for power pre-control.
Dependency: Refer to: p3520
Description: Display of the DC link voltage controller output (Vdc controller).
Index: [0] = I output
[1] = PI output
p3521[0...3] DC link pre-control power scaling / Vdc prectrl P scal
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7960
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-100000.00000 [%] 100000.00000 [%] 100.00000 [%]
r3522[0...4] CO: DC link voltage control pre-control display / DC_ctr prectr disp
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p3523[0...3] DC link pre-control power smoothing / Vdc pre-ctrl P sm
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 0 [ms]
r3554[0...1] Vdc controller output / INF Vdc_ctrl outp
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7960
P-Group: Closed-loop control Units group: 6_2 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]