2 Parameters
2.2 List of parameters
SINAMICS G130/G150
430 List Manual (LH2), 04/2014, A5E03263479A
5: SVM with pulse frequency reduction
6: SVM/FLB with pulse frequency reduction
7: No edge modulation up to 100 Hz
8: No edge modulation up to 60 Hz
9: Edge modulation
19: Optimized pulse pattern
Dependency: If a sine-wave filter is parameterized as output filter (p0230 = 3, 4), or if the power unit firmware is not able to
calculate edge modulation (r0192.0 = 0), then only space vector modulation without overcontrol can be set as
modulation type (p1802 = 3).
For permanent-magnet synchronous motors and chassis power units, the following applies:
Edge modulation or optimized pulse pattern can only be used, if p1810 bit 2 = 1 is set.
Refer to: r0192, p0230, p7003
Notice: If the pulse patterns are enabled with overmodulation option (p1802 < 3) or edge modulation (p1802 > 6), then the
current actual value correction is automatically activated (p1840.0 = 0).
Note: When modulation modes are enabled that could lead to overmodulation (p1802 = 0, 1, 2, 5, 6), the modulation depth
must be limited using p1803 (default p1803 < 100 %). The higher the overmodulation, the greater the current ripple
and torque ripple.
When changing p1802[x], the values for all of the other existing indices are also changed.
p1802 = 7, 8 should be used if the drive is operated below 100 Hz or 60 Hz, and it is necessary to avoid changing
over to edge modulation. Above these output frequencies, the modulation depth remains limited so that there the full
output voltage of the edge modulation is not reached.
The setting p1802 = 19 is only released for chassis power units and SIMOTICS FD motors.
Description: Defines the maximum modulation depth.
Note: p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
If an optimized pulse pattern is enabled (edge modulation), then the modulation depth is limited to below the output
frequency of 28 Hz as there is no optimized pulse pattern in this range.
Description: Filter time constant for the smoothed modulation index to change over the modulator mode.
Description: Sets the filter time constant of the DC link voltage used to calculate the modulation depth.
p1803[0...n] Maximum modulation depth / Modulat depth max
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6723
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
20.0 [%] 150.0 [%] 100.0 [%]
p1804[0...n] Filter time constant smoothed modulation index / T_filt mod_idxSmth
VECTOR_G Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [ms] 10000.0 [ms] 10.0 [ms]
p1806[0...n] Filter time constant Vdc correction / T_filt Vdc_corr
VECTOR_G Can be changed: U, T Calculated: CALC_MOD_REG Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [ms] 10000.0 [ms] 0.0 [ms]

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals