2 Parameters
2.2 List of parameters
SINAMICS G130/G150
170 List Manual (LH2), 04/2014, A5E03263479A
Description: Serial number part 5 of the encoder for the commissioning.
Dependency: Refer to: p0440, p0441, p0442, p0443, p0444, r0460, r0461, r0462, r0463, r0464
Note: A value of zero is displayed if an encoder is not present.
Description: Sets the number of bits before the absolute value in the SSI protocol.
Notice: When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Note: This parameter is automatically pre-set for encoders from the encoder list (p0400).
For example, error bit, alarm bit or parity bit can be positioned at these bits.
Description: Sets the number of bits for the absolute value in the SSI protocol.
Notice: When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Note: This parameter is automatically pre-set for encoders from the encoder list (p0400).
Description: Sets the number of bits after the absolute value in the SSI protocol.
Notice: This parameter is automatically pre-set for encoders from the encoder list (p0400).
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Note: For example, error bit, alarm bit or parity bit can be positioned at these bits.
p0445[0...n] Encoder commissioning serial number part 5 / Enc comm ser_no 5
ENC, VECTOR_G Can be changed: C2(4) Calculated: CALC_MOD_ALL Access level: 4
Data type: Unsigned32 Dyn. index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex
p0446[0...n] Encoder SSI number of bits before the absolute value / Enc SSI bit before
ENC, VECTOR_G Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0
p0447[0...n] Encoder SSI number of bits absolute value / Enc SSI bit val
ENC, VECTOR_G Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 25
p0448[0...n] Encoder SSI number of bits after the absolute value / Enc SSI bit after
ENC, VECTOR_G Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals