2 Parameters
2.2 List of parameters
SINAMICS G130/G150
552 List Manual (LH2), 04/2014, A5E03263479A
Displays the relative error of the current inversion(id(psid, iq) - id) / p2950:
idx4: error with respect to direct axis current for iq = 0
idx5: error with respect to direct axis current for iq = 0.5 * p2950
idx6: error with respect to direct axis current for iq = p2950
Index: [0] = d-current
[1] = d-flux iq0
[2] = d-flux iq1
[3] = d-flux iq2
[4] = d-current error iq0
[5] = d-current error iq1
[6] = d-current error q2
Note: The display is only generated when the pulses are inhibited.
Description: Sets the mode for the time stamp
p3100 = 0: Time stamp, operating hours
p3100 = 1: Time stamp, UTC format
p3100 = 2: Time stamp, operating hours + 01.01.2000
Notice: The realtime format (p3100 = 1), once selected, remains until the next time that the system is switched off. Switching
back to operating hours (p3100 = 0) or operating hours + 01.01.2000 (p3100=2) is prevented.
Note: RTC: Real-time clock
UTC: Universal Time Coordinates
The UTC time started, according to the definition on 01.01.1970 at 00:00:00 and is output in days and milliseconds.
Description: Setting the UTC time.
This means that the drive system is synchronized to the time specified by the time master.
To start p3101[1] must be written to followed by p3101[0]. After writing to p3101[0], the UTC time is accepted.
p3101[0]: Milliseconds
p3101[1]: Days
Description: Displays the actual UTC time in the drive system.
p3102[0]: Milliseconds
p3102[1]: Days
p3100 RTC time stamp mode / RTC t_stamp mode
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 2
p3101[0...1] RTC set UTC time / RTC set UTC
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 4294967295 0
r3102[0...1] RTC read UTC time / RTC read UTC
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals