EasyManuals Logo
Home>Siemens>Media Converter>SINAMICS G150

Siemens SINAMICS G150 User Manual

Siemens SINAMICS G150
1842 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #251 background imageLoading...
Page #251 background image
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
251
2 Parameters
2.2 List of parameters
Description: Sets the signal source to select the Drive Data Set, bit 3 (DDS, bit 3).
Dependency: Refer to: r0051, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source to select the Drive Data Set, bit 4 (DDS, bit 4).
Dependency: Refer to: r0051, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the freely-assignable motor number for the motor changeover.
Dependency: Refer to: p0827
Notice: When changing over motor data sets with the same motor number (e.g. star-delta changeover) and for a motor with
brake, the motor brake remains open during the changeover.
Note: When the motor data sets are changed over, the following applies:
The same motor number signifies the same thermal model.
For the same motor number, the correction values of the Rs, Lh or kT adaptation are applied for the data set
changeover (refer to r1782, r1787, r1797).
Description: Sets the bit number for every motor data set.
Example:
p0827[0] = 0: For MDS0, r0830.0 is switched.
p0827[1] = 5: For MDS1, r0830.5 is switched.
Dependency: Refer to: p0826, r0830
p0823[0...n] BI: Drive Data Set selection DDS bit 3 / DDS select., bit 3
VECTOR_G Can be changed: C2(15), T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 8565
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p0824[0...n] BI: Drive Data Set selection DDS bit 4 / DDS select., bit 4
VECTOR_G Can be changed: C2(15), T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 8565, 8575
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p0826[0...n] Motor changeover motor number / Mot_chng mot No.
VECTOR_G Can be changed: C2(3) Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: MDS, p0130 Func. diagram: 8575
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 15 0
p0827[0...n] Motor changeover status word bit number / Mot_chg ZSW bitNo.
VECTOR_G Can be changed: C2(3) Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: MDS, p0130 Func. diagram: 8575
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 15 0

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals