SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
109
2 Parameters
2.2 List of parameters
Note: When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined
SIEMENS filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside
the commissioning phase (p0010 = 0) and then the controller calculation (p0340 = 3) is carried out.
Description: Enters the capacitance of a sine-wave filter connected at the power unit output.
Dependency: This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the power
unit.
Refer to: p0230
Note: The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground).
When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined
SIEMENS filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside
the commissioning phase (p0010 = 0).
Description: Sets the number of reactors connected in series at the power unit output.
Dependency: Refer to: p0230
Notice: If the number of motor reactors connected in series does not correspond to this parameter value, then this can result
in an unfavorable control behavior.
Description: Displays the internal resistance of the power unit (IGBT and line resistance).
Note: For a parallel circuit, the value corresponds to the resistance of a power unit.
Description: Sets the configuration for the voltage measurement.
p0234 Power unit sine-wave filter capacitance / PU sine filter C
VECTOR_G Can be changed: C2(2), U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [µF] 1000.000 [µF] 0.000 [µF]
p0235 Motor reactor in series number / L_mot in SeriesQty
VECTOR_G Can be changed: C2(1, 2) Calculated: - Access level: 1
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 3 1
r0238 Internal power unit resistance / PU R internal
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
p0247 Voltage measurement configuration / U_mes config
VECTOR_G Can be changed: C2(2), U, T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
05 Use voltage measured values for flying
restart
Yes No -