2 Parameters
2.2 List of parameters
SINAMICS G130/G150
560 List Manual (LH2), 04/2014, A5E03263479A
Bits 20, 19, 18, 17, 16 = 1, 0, 0, 1, 0 --> PROFIdrive message class 18: error in the
parameterization/configuration/commissioning sequence
Bits 20, 19, 18, 17, 16 = 1, 0, 0, 1, 1 --> PROFIdrive message class 19: general drive fault
Description: Displays the fault value of the oldest active fault.
Dependency: Refer to: r2131, r3132
Description: Displays the component number of the oldest fault that is still active.
Dependency: Refer to: r2131, r3131
Description: Sets the suppression of r2139.3 "Fault present" for certain fault responses.
Dependency: Refer to: p0491, r2139
Note: Depending on the suppression of a fault reaction in this parameter, r2139.1 "Acknowledgement required" is set when
at least one fault occurs.
Re bit 08:
The suppression is only effective if p0491 = 1.
Description: Sets the threshold value for the "excitation current outside tolerance" message for the excitation current monitoring.
If the absolute value of the difference between the excitation current setpoint and actual value (r1641 - r1626)
exceeds the threshold value and the hysteresis is longer than the selected delay time, then fault F07913 is output.
This fault is withdrawn when the threshold voltage is undershot.
Dependency: Refer to: r1626, r1641, p3202, p3203
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
r3131 CO: Actual fault value / Act fault val
All objects Can be changed: - Calculated: - Access level: 3
Data type: Integer32 Dyn. index: - Func. diagram: 8060
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r3132 CO: Actual component number / Comp_no act
All objects Can be changed: - Calculated: - Access level: 3
Data type: Integer32 Dyn. index: - Func. diagram: 8060
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p3135 Suppress active fault / Supp act flt
B_INF, VECTOR_G Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: - Func. diagram: 8060
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
08 Suppression of fault response ENCODER ON OFF -
10 Suppression of fault response NONE ON OFF -
p3201[0...n] Excitation current outside the tolerance threshold value / I_exc n Tol thresh
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.1 [%] 100.0 [%] 10.0 [%]