2 Parameters
2.2 List of parameters
SINAMICS G130/G150
836 List Manual (LH2), 04/2014, A5E03263479A
Description: Supplies the number of entries in p9222.
Dependency: In p9221, the component Id is set whose statistic entries are to be displayed.
Refer to: p9221
Description: Selects the component Id whose statistics are to be displayed in p9222.
Description: Represents the statistic of acyclic Drive-CLiQ communication.
The component is preset in p9221.
The entry comprises the following elements:
Index 0: Parameter Id
Index 1: Number of messages sent.
Index 2: Minimum time of all acyclic requests referred to the parameter Id (index 0).
Index 3: Maximum time of all acyclic requests referred to the parameter Id (index 0).
Index 4: Average of all acyclic requests referred to the parameter Id (index 0).
The time unit is 10us.
Dependency: The number of statistic entries is displayed in p9220.
In p9221, the component Id can be set whose statistic is to be displayed.
Refer to: r9220, p9221
Note: As a statistic entry comprises 5 data, when calling the entries via the terminal, a size that represents a multiple of 5
must be specified.
Example: the 2nd entry must be called:
rdp 1 9222 5 5
or
rdpa 1 9222 5 5.
r9220 Statistic number of entries / Statistic size
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p9221 Statistic components Id / Statistic compId
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: T Calculated: - Access level: 4
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex 00FF hex 0002 hex
r9222[0...n] Statistic Drive-CLiQ acyclic communication / Statistic
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: r9220 Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -