2 Parameters
2.2 List of parameters
SINAMICS G130/G150
854 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the delay time for STOP A after STOP B / SS1.
In the case of encoderless motion monitoring functions with safe brake ramp monitoring (p9306 = 1) and the OFF3
ramp enabled at the same time (p9507.3 = 0), the parameter has no effect.
Dependency: Refer to: p9360, p9556
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
SS1: Safe Stop 1
Description: Sets the time after which STO must be active when initiating the test stop.
Dependency: Refer to: p9557
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
Description: Sets the maximum time for the acceptance test mode.
If the acceptance test mode takes longer than the selected time limit, then the mode is automatically terminated.
Dependency: Refer to: p9558
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
Description: Sets the shutdown velocity for activating STO.
Below this velocity "standstill" is assumed and for STOP B / SS1, STO is selected.
In the case of encoderless motion monitoring functions, the parameter must be > 0 (recommended value: 10).
Dependency: Refer to: p9356, p9560
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
p9356 SI Motion STOP A delay time (Motor Module) / SI Mtn IL t_del MM
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2819
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [µs] 3600000000.00 [µs] 100000.00 [µs]
p9357 SI Motion STO test time (Motor Module) / SI Mtn IL t MM
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [µs] 10000000.00 [µs] 100000.00 [µs]
p9358 SI Motion acceptance test mode time limit (Motor Module) / SI Mtn acc t MM
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
5000000.00 [µs] 100000000.00 [µs] 40000000.00 [µs]
p9360 SI Motion STO shutdown velocity (Motor Module) / SI Mtn IL v_sh MM
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [mm/min] 6000.00 [mm/min] 0.00 [mm/min]