2 Parameters
2.2 List of parameters
SINAMICS G130/G150
88 List Manual (LH2), 04/2014, A5E03263479A
Notice: It is not permissible to de-activate drive objects with safety functions enabled.
Note: The activation of a component can be rejected if the component was inserted for the first time. In this case, it is only
possible to activate the component when the pulses for all of the drive objects are inhibited.
For units connected in parallel, when one of the power units is de-activated, then the enable in p7001 is withdrawn.
Re value = 0, 2:
When a component is deactivated it no longer outputs any errors.
If value = 0:
The component was completely commissioned and is deactivated using this value. It can be removed from the
DRIVE-CLiQ without any error.
If value = 1:
The component must be available for error-free operation.
If value = 2:
A component in a project generated offline and set to this value must never be inserted in the actual topology from
the very start. This means that the component is marked to be bypassed in the DRIVE-CLiQ line.
For components that comprise several individual components (e.g. Double Motor Modules), it is not permissible to
set just one subset to this value.
Description: Displays the "active/inactive" state of a power unit component.
Value: 0: Component inactive
1: Component active
Dependency: Refer to: p0105, p0125, p0897
Description: Displays the version of the EEPROM data of the power unit.
Dependency: Refer to: r0147, r0157
Note: For parallel circuit configurations, the parameter index is assigned to a power unit.
Description: Displays the firmware version of the power unit.
Dependency: Refer to: r0018, r0148, r0158, r0197, r0198
Note: Example:
The value 1010100 should be interpreted as V01.01.01.00.
For parallel circuit configurations, the parameter index is assigned to a power unit.
r0126[0...n] Power unit components active/inactive / PU comp act/inact
B_INF, VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Integer16 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 -
r0127[0...n] Power unit EEPROM data version / PU EEPROM version
B_INF, VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r0128[0...n] Power unit firmware version / PU FW version
B_INF, VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -