Description: Sets the type of technology controller.
Value: 0: D component in the actual value signal
1: D component in the fault signal
Description: Sets the signal source for the actual value of the technology controller.
Description: Sets the time constant for the actual value filter (PT1) of the technology controller.
Description: Display and connector output for the smoothed actual value after the filter (PT1) of the technology controller.
Description: Sets the upper limit for the actual value signal of the technology controller.
Dependency: Refer to: p2252, p2264, p2265, p2271
Notice: If the actual value exceeds this upper limit, this results in fault F07426.
Note: Limiting only active for p2252.3 = 1.
p2263 Technology controller type / Tec_ctrl type
VECTOR_G
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p2264[0...n] CI: Technology controller actual value / Tec_ctrl act val
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 0
p2265 Technology controller actual value filter time constant / Tec_ctrl act T
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
r2266 CO: Technology controller actual value after filter / Tec_ctr act aftFlt
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p2267 Technology controller upper limit actual value / Tec_ctrl u_lim act
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-10000.00 [%] 10000.00 [%] 200.00 [%]

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals