SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
611
2 Parameters
2.2 List of parameters
Description: Sets the scaling characteristic for the analog inputs of Terminal Board 30 (TB30).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the scaling characteristic for the analog inputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Notice: This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the response threshold for wire-breakage monitoring of the analog inputs of Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency: For the following analog input type, the wire breakage monitoring is active:
p4056[x] = 3 (unipolar current input monitored (+4 mA ... +20 mA))
Refer to: r4056, p4056
Description: Sets the delay time for wire-breakage monitoring of the analog inputs on Terminal Module 31 (TM31).
p4060[0...1] TB30 analog inputs characteristic value y2 / TB30 AI char y2
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 100.00 [%]
p4060[0...1] TM31 analog inputs characteristic value y2 / TM31 AI char y2
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 100.00 [%]
p4061[0...1] TM31 analog inputs wire breakage monitoring response threshold /
TM31 WireBrkThresh
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [mA] 20.00 [mA] 2.00 [mA]
p4062[0...1] TM31 analog inputs wire breakage monitoring delay time / TM31 wirebrk t_del
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 100 [ms]

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals