2 Parameters
2.2 List of parameters
SINAMICS G130/G150
118 List Manual (LH2), 04/2014, A5E03263479A
Description: Threshold to detect a DC link undervoltage.
If the DC link voltage falls below this threshold, the drive unit is tripped due to a DC link undervoltage condition.
Note: The value depends on the device type and the selected device rated voltage (p0210).
Description: Threshold to detect a DC link undervoltage.
If the DC link voltage falls below this threshold, the drive unit is tripped due to a DC link undervoltage condition.
Dependency: Refer to: p0278
Note: The value depends on the device type and the selected device rated voltage (p0210).
For booksize drive units, the following applies:
The undervoltage threshold can be reduced with p0278.
Description: Threshold to detect a DC link overvoltage.
If the DC link voltage exceeds the threshold specified here, the drive unit is tripped due to DC link overvoltage.
Description: Selects the motor type or starts to read in the motor parameters for a motor with DRIVE-CLiQ (p0300 = 10000 or
10001, if there is a second data set).
For p0300 < 10000 the following applies:
The first digit of the parameter value always defines the general motor type and corresponds to the third-party motor
belonging to a motor list:
1 = Rotating induction motor
2 = Rotating synchronous motor
3 = Linear induction motor (reserved)
4 = Linear synchronous motor
r0296 DC link voltage undervoltage threshold / Vdc U_lower_thresh
B_INF Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 8750, 8760,
8850, 8864, 8950, 8964
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r0296 DC link voltage undervoltage threshold / Vdc U_lower_thresh
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r0297 DC link voltage overvoltage threshold / Vdc U_upper_thresh
B_INF, VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 8750, 8760,
8850, 8864, 8950, 8964
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
p0300[0...n] Motor type selection / Mot type sel
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: Integer16 Dyn. index: MDS, p0130 Func. diagram: 6310
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 10001 0