SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
431
2 Parameters
2.2 List of parameters
Description: DC link voltage that is used to convert the setpoint voltage into an equivalent modulation depth.
Description: DC link voltage used to determine the maximum possible output voltage.
Description: Displays the effective modulator mode.
Value: 1: Flat top modulation (FLB)
2: Space vector modulation (SVM)
3: Edge modulation from 28 Hz; 23:3
4: Edge modulation from 28 Hz; 19:1
5: Edge modulation from 60 Hz; 17:3
6: Edge modulation from 60 Hz; 17:1
7: Edge modulation from 100 Hz; 9:2
8: Edge modulation from 100 Hz; 9:1
9: Optimized pulse pattern
Description: Sets the configuration for the modulator.
r1807 Actual DC link voltage to calculate the modulation depth / VdcActValMod_depth
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: 5_2 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r1808 DC link voltage actual value for U_max calculation / Vdc act val U_max
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: 5_2 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r1809 CO: Modulator mode actual / Modulator mode act
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 9 -
p1810 Modulator configuration / Modulator config
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0010 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Avg value filter for U_lim (only for
Vdc_comp. in modulator)
Yes No -
01 DC link voltage compensation in the current
control
Yes No -
02 Wobbulation activated Yes No -
03 Current measurement oversampling
selected
Yes No -
08 Pulse frequency reduction (speed
dependent) stage 1
Yes No -

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals