SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
717
2 Parameters
2.2 List of parameters
The counter state corresponds to the valve wear. A maximum of 650% of the specified service life is displayed.
10000 corresponds to the nominal service life (100%). When this value is reached, the IGBT is theoretically at the
end of its service life and must be replaced.
Dependency: Refer to: p7786
Notice: After a valve has been replaced, the corresponding power cycling counter must be reset.
Note: The IGBT power cycling counter can only be set to 0.
Procedure when replacing valve 4:
1. Switch off the system and replace valve 4.
2. Switch on the system and acknowledge that valve 4 has been replaced (p7786.4 = 1).
--> the power cycling counter of valve 4 is reset (r7743 = 0).
3. Carry out a POWER ON (power off/on).
--> as a consequence p7786.4 is automatically set to 0.
Description: Displays the status of power cycling counter for valve 5.
For repairs, this parameter serves as internal documentation for service personnel.
The counter state corresponds to the valve wear. A maximum of 650% of the specified service life is displayed.
10000 corresponds to the nominal service life (100%). When this value is reached, the IGBT is theoretically at the
end of its service life and must be replaced.
Dependency: Refer to: p7786
Notice: After a valve has been replaced, the corresponding power cycling counter must be reset.
Note: The IGBT power cycling counter can only be set to 0.
Procedure when replacing valve 5:
1. Switch off the system and replace valve 5.
2. Switch on the system and acknowledge that valve 5 has been replaced (p7786.5 = 1).
--> the power cycling counter of valve 5 is reset (r7744 = 0).
3. Carry out a POWER ON (power off/on).
--> as a consequence p7786.5 is automatically set to 0.
Description: Displays the status of power cycling counter for valve 6.
For repairs, this parameter serves as internal documentation for service personnel.
The counter state corresponds to the valve wear. A maximum of 650% of the specified service life is displayed.
10000 corresponds to the nominal service life (100%). When this value is reached, the IGBT is theoretically at the
end of its service life and must be replaced.
Dependency: Refer to: p7786
Notice: After a valve has been replaced, the corresponding power cycling counter must be reset.
Note: The IGBT power cycling counter can only be set to 0.
Procedure when replacing valve 6:
1. Switch off the system and replace valve 6.
2. Switch on the system and acknowledge that valve 6 has been replaced (p7786.6 = 1).
--> the power cycling counter of valve 6 is reset (r7745 = 0).
r7744[0...n] IGBT power cycling counter valve 5 / IGBT load count 5
B_INF, VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r7745[0...n] IGBT power cycling counter valve 6 / IGBT load count 6
B_INF, VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals