2 Parameters
2.2 List of parameters
Description: Displays the period number determined by the vibration test.
Index: [0] = No. of periods of the low frequency
[1] = No. of periods of the high frequency
Dependency: Refer to: p1959
Description: Displays the number of pulses determined during the vibration test.
Note: A negative signal indicates an incorrect polarity of the encoder signal.
Description: Sets the maximum flux setpoint to measure the saturation characteristic.
Description: Displays the status to check and monitor the states of speed controller optimization.
r1972[0...1] Speed_ctrl_opt vibration test number of periods determined / n_opt per_qty det
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
- - -
r1973 Rotating measurement encoder test pulse number determined / n_opt puls no. det
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 3
Data type: Integer32 Dyn. index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
- - -
p1974 Speed_ctrl_opt saturation characteristic rotor flux maximum / n_opt rot_fl max
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
104 [%] 120 [%] 120 [%]
r1979.0...12 BO: Speed_ctrl_opt status / n_opt status
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Speed controller optimization activated Yes No -
01 Speed controller optimization completed Yes No -
02 Speed controller optimization interrupted Yes No -
04 Encoder test active Yes No -
05 Saturation char. identification active Yes No -
06 Moment of inertia identification active Yes No -
07 Recalc. speed controller parameters active Yes No -
08 Speed controller vibration test active Yes No -
09 Magnetizing inductance adapt. active Yes No -
10 Operation with encoder after encoderless
operation
Yes No -
11 q-leakage inductance identification Yes No -
12 Moment of inertia estimator inhibited Yes no -