2 Parameters
2.2 List of parameters
Description: Displays the MAC address for the onboard PROFINET interface on the Control Unit.
Description: Displays the state of the cyclic PROFINET connections.
For two connections (Shared Device) the display in the index depends on the sequence in which the connections are
established.
Value: 0: Interrupted
1: Not connected
2: Connection starts to be established
3: Module information expected
4: Module information received
5: Module address expected
6: Module address received
7: Parameterization data expected
8: Parameterization data received
9: Evaluate parameterization data
10: Connection being established completion expected
11: Configured controller RUN expected
12: Configured controller STOP
13: Configured controller RUN
Dependency: Refer to: p8929
Note: If value = 10:
If the connection remains in this state, then when using PROFINET IRT the following can apply:
- topology error (incorrect port assignment).
- synchronization missing.
Description: Display to diagnose the cyclic PROFINET connections.
Index: [0] = Number of cyclic connections
[1] = Number of send subslots of all connections
[2] = Number of send net data (bytes) of all connections
[3] = Number of receive subslots of all connections
[4] = Number of receive net data (bytes) of all connections
[5] = Connection type (RT, IRT)
Dependency: Refer to: p8929
r8935[0...5] PN MAC Address of Station / PN MAC of Station
CU_G130_PN,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex 00FF hex -
r8936[0...1] PN state cyclic connections / PN stat cyc conn
CU_G130_PN,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 13 -
r8937[0...5] PN diagnostics / PN diag
CU_G130_PN,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -