2 Parameters
2.2 List of parameters
SINAMICS G130/G150
702 List Manual (LH2), 04/2014, A5E03263479A
Description: Displays the deviation between the measured current actual value of phase U and the average value as peak value.
The maximum deviation from the average value is displayed in r7025.
Dependency: Refer to: r7021, r7022, r7025
Description: Displays the deviation between the measured current actual value of phase V and the average value as peak value.
The maximum deviation from the average value is displayed in r7026.
Dependency: Refer to: r7020, r7022, r7026
Description: Displays the deviation between the measured current actual value of phase W and the average value as peak value.
The maximum deviation from the average value is displayed in r7027.
Dependency: Refer to: r7020, r7021, r7027
Description: Displays the maximum absolute deviation of the measured current actual values of phase U from the average value
as peak value.
The deviation of the individual currents from the average value is displayed in r7020.
Dependency: Refer to: r7020, r7026, r7027
r7020[0...n] CO: Par_circuit deviation current in phase U / Phase U curr dev
VECTOR_G (Parallel) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Units group: 6_5 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r7021[0...n] CO: Par_circuit deviation current in phase V / Phase V curr dev
VECTOR_G (Parallel) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Units group: 6_5 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r7022[0...n] CO: Par_circuit deviation current in phase W / Phase W curr dev
VECTOR_G (Parallel) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Units group: 6_5 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r7025 CO: Par_circuit max. deviation currents phase U / Phase U Max i_dev
VECTOR_G (Parallel) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: 6_5 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]