2 Parameters
2.2 List of parameters
SINAMICS G130/G150
98 List Manual (LH2), 04/2014, A5E03263479A
Dependency: Refer to: r0193
Notice: This information represents the characteristics/features of the power unit firmware. It does not provide
information/data about the characteristics/features of the hardware (e.g. bit 06 = 1 means that although the firmware
supports "liquid cooling", a power unit with liquid cooling does not have to be used).
Note: Re bit 09:
The Motor Module supports the internal armature short-circuit. The function is internally required for voltage
protection (p1231 = 3).
Re bit 10:
The Motor Module supports the autonomous internal voltage protection.
If the "internal voltage protection" function is activated (p1231 = 3) the Motor Module decides autonomously - using
the DC link voltage - as to whether the short-circuit is activated.
Re bit 23:
The component supports the detection of current actual values (and the detection of valve close durations) with
double clocking and phase shift.
Description: Displays the properties supported by the power unit firmware.
Dependency: Refer to: r0192
Description: Displays the properties supported by the Voltage Sensing Module (VSM).
17 Compound braking possible Yes No -
18 Extended voltage range possible Yes No -
19 Gating unit available with current limitation
control
Yes No -
20 Component status possible Yes No -
21 Temperature evaluation via Motor Module /
CU terminals possible
Yes No -
22 Reduced device supply voltage possible Yes No -
23 Current measurement oversampling
available
Yes No -
24 Parking keeping the relevant data is
available
Yes No -
25 Internal fan operating hours counter
available
Yes No -
26 Software gating unit supported in the
Control Unit
Yes No -
27 Current controller dynamics higher Yes No -
28 Reserved -
29 Voltage measurement Yes No -
30 Gating unit with all-phase current limiting Yes No -
r0193 Power unit firmware properties 2 / PU FW property 2
B_INF, VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
01 Component trace Yes No -
r0194[0...n] VSM properties / VSM properties
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: p0150 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Reserved Yes No -