SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
405
2 Parameters
2.2 List of parameters
Index: [0] = Excitation ready to be powered up
[1] = Excitation ready
[2] = Excitation operational
[3] = Excitation group signal fault
[4] = Excitation group signal alarm
[5] = Not used
[6] = Not used
[7] = Excitation at the voltage limit
Dependency: Refer to: r1649
Description: Sets the monitoring time of the excitation.
After an ON command, the feedback signal must be received within this monitoring time.
Note: After the on command for the excitation (r1648.0 = 1), its feedback signal must be available at r1649.1 within this
monitoring time (BI: p1645[1]).
The same monitoring time is effective after the excitation is enabled for operation (r1648.3 = 1) up to the feedback
signal "excitation operational" (r1649.2 = 1, BI: p1645[2]).
Description: Sets the switch-off delay time to shut down the excitation equipment.
Note: The delay time starts if, when powering down, r0863.0 = 0.
r1648.0 and r1648.3 are reset at the end of the delay time.
Description: Displays the control word for the excitation equipment.
Note: Re bit 00:
This bit is set dependent on r0863.0.
p1646 Excitation monitoring time / Excit t_monit
VECTOR_G (n/M) Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6495
P-Group: Commands Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
2.0 [s] 1300.0 [s] 20.0 [s]
p1647 Excitation switch-off delay time / Exc t_off
VECTOR_G (n/M) Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6495
P-Group: Commands Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.0 [s] 5.0 [s] 0.8 [s]
r1648.0...11 CO/BO: Excitation control word / Excitation STW
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 6495
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Power up excitation Yes No -
01 Excitation no OFF2 Yes No -
02 Excitation no OFF3 Yes No -
03 Excitation operation enable Yes No -
07 Excitation acknowledge fault Yes No -
10 Master control by excitation equipment Yes No -
11 ccw rotating field excitation invert excitation
current setpoint
Yes No -

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals