2 Parameters
2.2 List of parameters
SINAMICS G130/G150
332 List Manual (LH2), 04/2014, A5E03263479A
Description: Displays the status word for armature short-circuit.
Dependency: Refer to: p1230, p1231, p1232, p1233, p1234, p1235, p1236, p1237
Note: External armature short-circuit (bits 0 ... 3):
Re bit 00:
Using this signal, the motor is short-circuited through an external contactor circuit. This means that this BO: p1239.0
must be interconnected e.g. to a digital output.
Re bit 01:
This signal indicates the state of the contactor to establish the armature short-circuit. To do this, BI: p1235 must be
interconnected to a digital input.
Re bit 02:
The external armature short-circuit configuration is ready and is activated as soon as the activation criterion is
fulfilled.
Re bit 03:
1: A feedback signal from an external contactor was parameterized in BI: p1235.
Internal voltage protection / internal armature short-circuit (bits 4 ... 6):
Re bit 04:
a) Internal voltage protection (p1231 = 3) was selected and the Motor Module does not support the autonomous
internal voltage protection (r0192.10 = 0).
The Control Unit issues the command to the Motor Module to short-circuit the motor through the power
semiconductors.
a) Internal voltage protection (p1231 = 3) was selected and the Motor Module supports the autonomous internal
voltage protection (r0192.10 = 1).
The Motor Module decides autonomously whether the armature short-circuit is activated. In this case, the following
applies: r1239.4 = r1239.5.
c) Internal armature short-circuit (p1231 = 4) was selected.
The Control Unit issues the command to the Motor Module to short-circuit the motor through the power
semiconductors.
Re bit 05:
The Motor Module signals that the motor is short-circuited in the Motor Module through the power semiconductors.
r1239.0...13 CO/BO: Armature short-circuit / DC braking status word / ASC/DCBRK ZSW
VECTOR_G Can be changed: - Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 External armature short-circuit Active Inactive -
01 External armature short-circuit contactor
feedback signal
Closed Open -
02 External armature short-circuit ready Yes No -
03 External armature short-circuit with
contactor feedback signal
Yes No -
04 Internal armature short-circuit Active Inactive -
05 Internal armature short circuit feedback
signal from power unit
Active Inactive -
06 Internal armature short-circuit ready Yes No -
08 DC braking active Yes No 7017
09 DC current injection active Yes No -
10 DC braking ready Yes No 7017
11 Armature short circuit/DC braking selected Yes No -
12 DC braking selection internally inhibited Yes No -
13 DC braking for OFF1/OFF3 Yes No -