SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
353
2 Parameters
2.2 List of parameters
Note: Linear interpolation is carried out between the points 0 Hz/p1310, p1320/p1321 ... p1326/p1327. For output
frequencies above p1326, the characteristic is extrapolated with the gradient between the characteristic points
p1324/p1325 and p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable U/f characteristic.
Description: The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the fourth point along the characteristic.
Dependency: Selects the freely programmable characteristic using p1300 = 3.
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1324, p1325, p1326
Note: Linear interpolation is carried out between the points 0 Hz/p1310, p1320/p1321 ... p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable U/f characteristic.
Description: Sets the signal source for the voltage setpoint for U/f control with an independent voltage setpoint (p1300 = 19).
Dependency: Selects the U/f control with independent voltage setpoint via p1300 = 19.
Refer to: p1300
Description: Limiting the voltage setpoint.
This means that the output voltage can be reduced with respect to the calculated maximum voltage r0071 and the
start of field weakening.
Note: The output voltage is only limited if, as a result of p1331, the maximum output voltage (r0071) is fallen below.
Description: Sets the starting frequency at which FCC (Flux Current Control) is activated.
Dependency: The correct operating mode must be set (p1300 = 1, 6).
Warning: An excessively low value can result in instability.
p1327[0...n] U/f control programmable characteristic voltage 4 / Uf char U4
VECTOR_G Can be changed: U, T Calculated: CALC_MOD_REG Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6301
P-Group: U/f open-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [Vrms] 10000.0 [Vrms] 0.0 [Vrms]
p1330[0...n] CI: U/f control independent voltage setpoint / Uf U_set independ.
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 6301
P-Group: U/f open-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- - 0
p1331[0...n] Voltage limiting / U_lim
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6300
P-Group: - Units group: 5_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
50.00 [Vrms] 2000.00 [Vrms] 1000.00 [Vrms]
p1333[0...n] U/f control FCC starting frequency / U/f FCC f_start
VECTOR_G Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6301
P-Group: U/f open-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]