2 Parameters
2.2 List of parameters
SINAMICS G130/G150
212 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the bearing version.
Corresponding to the bearing version entered, its code number (p0531) is automatically set.
0 = No selection
1 = Manual entry
101 = STANDARD
102 = PERFORMANCE
103 = HIGH PERFORMANCE
104 = ADVANCED LIFETIME
Dependency: Refer to: p0301, p0531, p0532, p1082
Notice: For p0530 = 101, 102, 103, 104, the maximum bearing speed (p0532) is write protected. Write protection is
withdrawn with p0530 = 1.
If p0530 is changed during quick commissioning (p0010 = 1), then the maximum speed p1082, which is also
associated with quick commissioning, is pre-assigned appropriately. This is not the case when commissioning the
motor (p0010 = 3). The maximum speed of the bearing is factored into the limit for the maximum speed p1082.
Note: For a motor with DRIVE-CLiQ, p0530 can only be set to 1.
Description: Display and setting the code number of the bearing.
When setting p0301 and p0530 the code number is automatically preassigned and is write protected. The information
in p0530 should be observed when removing write protection.
Dependency: Refer to: p0301, p0530, p0532, p1082
Notice: If p0531 is changed during quick commissioning (p0010 = 1), then the maximum speed p1082, which is also
associated with quick commissioning, is pre-assigned appropriately. This is not the case when commissioning the
motor (p0010 = 3). The maximum speed of the bearing is factored into the limit for the maximum speed p1082.
Note: p0531 cannot be changed on a motor with DRIVE-CLiQ.
Description: Sets the maximum speed of the bearing.
The following applies when calculating the maximum speed (p1082):
- for p0324 = 0 or p0532 = 0, p0322 is used.
- for p0324 > 0 and p0532 > 0, the minimum value from the two parameters is used.
Dependency: Refer to: p0301, p0322, p0324, p0530, p1082
p0530[0...n] Bearing version selection / Bearing vers sel
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: Unsigned16 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: FEM Scaling: - Expert list: 1
Min Max Factory setting
0 104 0
p0531[0...n] Bearing code number selection / Bearing codeNo sel
VECTOR_G Can be changed: C2(3) Calculated: - Access level: 1
Data type: Unsigned16 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: FEM Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0
p0532[0...n] Bearing maximum speed / Bearing n_max
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: FEM Scaling: - Expert list: 1
Min Max Factory setting
0.0 [rpm] 210000.0 [rpm] 0.0 [rpm]

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals