2 Parameters
2.2 List of parameters
Warning: When activating the essential service mode (BI: p3880 = 1 signal), the motor immediately runs according to the
selected setpoint source. When the essential service mode is activated, the motor cannot be stopped using the OFF
commands.
Note: ESM: Essential Service Mode
Permissible signal sources:
- BO: r0722.x (high active)
- BO: r0723.x (low active), x = 0 ... 17, 20, 21
Description: Sets the setpoint source for essential service mode (ESM).
Value: 0: Last known setpoint (r1078 smoothed)
1: Fixed speed setpoint 15 (p1015)
3: Fieldbus
5: TB30/TM31 analog input
6: Enable the response OFF1
7: Enable the response OFF2
Note: ESM: Essential Service Mode
When the essential service mode is activated, the effective speed setpoint is displayed in r1114.
Re p3881 = 0:
The last known setpoint value is only transmitted safely if it was present consistently for at least 30 s prior to
activating the essential service mode. If this condition is not met, fixed speed setpoint 15 (p1015) is used.
Re p3881 = 5:
The signal source for the setpoint via analog input for TB30/TM31 is set via p3886.
Re p3881 = 6:
n_act = 0: pulse cancellation and switching-on inhibited.
n_active > 0: braking along the ramp-function generator down ramp (p1121), pulse cancellation and switching-on
inhibited.
Re p3881 = 7:
n_act = 0: pulse cancellation and switching-on inhibited.
n_act > 0: immediate pulse cancellation and switching-on inhibited.
Description: Sets the alternative setpoint source for essential service mode (ESM).
This setpoint is used when the setpoint source set in p3881 is lost.
Value: 0: Last known setpoint (r1078 smoothed)
1: Fixed speed setpoint 15 (p1015)
2: Maximum speed (p1082)
Dependency: Refer to: p3881
Note: ESM: Essential Service Mode
The alternative setpoint source is only active for p3881 = 3, 5.
p3881 ESM setpoint source / ESM setp_src
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 7033
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 7 0
p3882 ESM setpoint source alternative / ESM setp_src alt
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 7033
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 0