SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
991
2 Parameters
2.2 List of parameters
Description: Displays the events that lead to the transfer of failsafe signals to all drives assigned to the TM54F. If the second
channel of the TM54F transmits failsafe signals, then these are synchronized to the other channel. In this particular
case, p10054 of the other TM54F channel should be evaluated.
Possibilities of resolving the situation:
- error during test stop: correctly perform the test stop.
- internal software error: no possibility of resolving this problem, POWER ON.
- internal synchronization problem: no possibility of resolving this problem, POWER ON.
- internal status error: no possibility of resolving this problem, POWER ON.
- parameterizing error: evaluate description of alarms F35004 or F35006. Resolve parameterizing error. POWER ON.
After updating the firmware of the TM54F it is possible that a power on is required.
- all other causes: remove the cause of the error and carry out a safe acknowledgment (p10006).
Description: Displays the communication status of the individual drives with the Terminal Module 54F (TM54F).
For r10055 = 0, the following applies:
All drives assigned in p10010 communicate with the TM54F.
r10054 SI TM54F failsafe events active / SI failsafe act
TM54F_MA,
TM54F_SL
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Commissioning mode active (p0010 = 95) Yes No 2847
01 Checksum error of the safety parameters Yes No -
02 Internal synchronization problem within
TM54F
Yes No -
03 Internal software error Yes No -
04 Overvoltage in the TM54F Yes No -
05 Undervoltage in the TM54F Yes No -
06 Error at test stop Yes No -
07 Error for crosswise data comparison within
TM54F
Yes No -
08 Overtemperature in the TM54F Yes No -
09 Internal status error Yes No -
10 Param error Yes No -
31 Failsafe events active on another channel Yes No -
r10055 SI TM54F communication status drive-specific / SI comm_stat drv
TM54F_MA,
TM54F_SL
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Communication between drive 1 and
TM54F
Not configured Configured -
01 Communication between drive 2 and
TM54F
Not configured Configured -
02 Communication between drive 3 and
TM54F
Not configured Configured -
03 Communication between drive 4 and
TM54F
Not configured Configured -
04 Communication between drive 5 and
TM54F
Not configured Configured -
05 Communication between drive 6 and
TM54F
Not configured Configured -

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals