List Manual (LH2), 04/2014, A5E03263479A
245
2 Parameters
2.2 List of parameters
Description: Sets an additional offset for the test sockets.
Index: [0] = T0
[1] = T1
[2] = T2
Description: Sets the limit for a signal to be output via test sockets.
Value: 0: Limiting off
1: Limiting on
Index: [0] = T0
[1] = T1
[2] = T2
Note: Limiting on:
If signals are output outside the permissible measuring range, the signal is limited to 4.98 V or to 0 V.
Limiting off:
If signals are output outside the permissible measuring range, this causes signal overflow. In the case of signal
overflow, the signal jumps from 0 V to 4.98 V or from 4.98 V to 0 V.
Description: Displays the scaling of the signal to be output.
A change in the output voltage by 1 volt corresponds to the value in this parameter. The units are determined by the
interconnected test signal.
Index: [0] = T0
[1] = T1
[2] = T2
Dependency: Refer to: p0771, r0772, r0774, p0777, p0778, p0779, p0780, p0783, p0784
Note: Example:
r0786[0] = 1500.0 and the measuring signal is r0063 (CO: Actual speed smoothed [rpm]).
A change of 1 V at the output of test socket T0 corresponds to 1500.0 [rpm].
p0783[0...2] Test sockets offset / Test skt offset
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8134
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-4.98 [V] 4.98 [V] 0.00 [V]
p0784[0...2] Test socket limit on/off / TestSktLim on/off
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 8134
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
r0786[0...2] Test socket scaling per volt / TestSktScale/Volt
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8134
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -