EasyManuals Logo
Home>Siemens>Media Converter>SINAMICS G150

Siemens SINAMICS G150 User Manual

Siemens SINAMICS G150
1842 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #437 background imageLoading...
Page #437 background image
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
437
2 Parameters
2.2 List of parameters
Description: Sets the valve lockout time to compensate for phase U.
Notice: The deadtime compensation is deactivated with p7003 = 2.
Note: The value is automatically calculated in the motor data identification routine.
For type PM340 power units, the value is limited to 3.98 µs.
Description: Sets the valve lockout time to compensate for phase V.
Notice: The deadtime compensation is deactivated with p7003 = 2.
Note: For type PM340 power units, the value is limited to 3.98 µs.
Description: Sets the valve lockout time to compensate for phase W.
Notice: The deadtime compensation is deactivated with p7003 = 2.
Note: For type PM340 power units, the value is limited to 3.98 µs.
Description: Sets the current level for the dead time compensation.
Above the current level, the dead time - resulting from the converter switching delays - is compensated by a
previously calculated constant value. If the relevant phase current setpoint falls below the absolute value defined by
p1832, the corrective value for this phase is continuously reduced.
Dependency: The factory setting of p1832 is automatically set to 0.02 * rated drive converter current (r0207).
p1828 Compensation valve lockout time phase U / Comp t_lock ph U
VECTOR_G Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [µs] 1000000.00 [µs] 0.00 [µs]
p1829 Compensation valve lockout time phase V / Comp t_lock ph V
VECTOR_G Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [µs] 1000000.00 [µs] 0.00 [µs]
p1830 Compensation valve lockout time phase W / Comp t_lock ph W
VECTOR_G Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [µs] 1000000.00 [µs] 0.00 [µs]
p1832 Dead time compensation current level / t_dead_comp I_lev
VECTOR_G Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [Arms] 10000.0 [Arms] 0.0 [Arms]

Table of Contents

Other manuals for Siemens SINAMICS G150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G150 and is the answer not in the manual?

Siemens SINAMICS G150 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G150
CategoryMedia Converter
LanguageEnglish

Related product manuals