Page 132 © 2022 Smartrise Engineering, Inc. All Rights Reserved October 2022
14.20 Hourly Fault Limit
The hourly fault is the number of door faults allowed per hour prior to the car going out of
service. The car remains out of service until the hour window elapses.
The following procedure describes how to set the hourly fault limit.
Navigate to MAIN MENU | SETUP | DOOR SETUP. See Figure 55.
From the DOORS menu, scroll and select Hourly Fault Limit.
Figure 218: DOORS Menu – Hourly Fault Limit
From the HOURLY FAULT LIMIT menu, set the number of logged faults allowed per hour
before the car goes out of service.
Figure 219: HOURLY FAULT LIMIT Menu
Scroll right and press Save.
14.21 Nudge – Buzzer Only
When enabled during nudging, the Nudge (NDG) output is disabled and only the buzzer sounds.
The following procedure describes how to only enable the buzzer during nudging.
Navigate to MAIN MENU | SETUP | DOOR SETUP. See Figure 55.
From the DOORS menu, scroll and select Nudge – Buzzer Only.
Figure 220: DOORS Menu – Nudge – Buzzer Only