Hydro:Evolved User Manual
October 2022 © 2022 Smartrise Engineering, Inc. All Rights Reserved Page 257
31.3.4 Alternate Smoke
The alternate smoke is where the car is recalled to an alternate designated landing when smoke
has been detected in the main lobby.
31.3.4.1 Main or Alternate
The car travels to the main landing when smoke has been detected. If configured and the
smoke is on that floor, the car travels to an alternated landing.
The following procedure describes if the car travels to the main or alternate designated landing
when smoke has been detected.
Navigate to MAIN MENU | SETUP | FIRE. See Figure 56.
From the FIRE SERVICE menu, scroll and select Alt Smoke.
Figure 479: FIRE SERVICE Menu Alt Smoke
From the ALT SMOKE menu, scroll and select Main or Alt.
Figure 480: ALT SMOKE Menu Main or Alt
From the USE ALT FLOOR menu, scroll and select if the alternate floor is configured for
alternate smoke.
Figure 481: USE ALT FLOOR Menu
Scroll right and press Save.

Table of Contents

Other manuals for Smartrise HYDRO:EVOLVED

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Smartrise HYDRO:EVOLVED and is the answer not in the manual?

Smartrise HYDRO:EVOLVED Specifications

General IconGeneral
BrandSmartrise
ModelHYDRO:EVOLVED
CategoryController
LanguageEnglish

Related product manuals