Hydro:Evolved User Manual
Page 154 © 2022 Smartrise Engineering, Inc. All Rights Reserved October 2022
16 Hall Network
The hall network is a group of Hall boards connected by a CAN bus.
16.1 CAN Bus
Each Hall board communicates over a CAN bus to a Riser board located in the machine room.
The figure below shows a standard CAN network. For optimal performance, the cable stub
lengths should be kept short and only node 1 and node 4 on the CAN bus line should be
terminated.
Figure 258: Standard CAN Bus
1
Termination The first and last boards within each CAN network are terminated. See section
2.3 I/O Board/Riser Board SR3031 for more information.
Example 1 A single set of hall buttons are wired to Riser board 1.
The Riser board’s CAN2 termination and the bottom landing Hall board’s
termination is set.
Example 2 Two sets of Hall buttons are both wired to Riser board 1.
The bottom landing Hall board for each Hall board set is terminated. The Riser
board’s CAN2 is NOT terminated. For tall buildings, the second set of Hall boards
may need to be split off and connected to a second Riser board. Both networks are
terminated as described in example 1.
1
See https://www.onsemi.com/pub/Collateral/AND8376-D.PDF for CAN Bus with Unterminated Stubs

Table of Contents

Other manuals for Smartrise HYDRO:EVOLVED

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Smartrise HYDRO:EVOLVED and is the answer not in the manual?

Smartrise HYDRO:EVOLVED Specifications

General IconGeneral
BrandSmartrise
ModelHYDRO:EVOLVED
CategoryController
LanguageEnglish

Related product manuals