cars are manually selected via the select inputs if Auto Select is
inactive.
Car is on generator power. Generator has spun up and cars can
begin recalling one at a time to the lobby where they will hold
doors open.
Table 35: Description of Fire/Earthquake Inputs
Initiates the hoistway scan for earthquake at low speed.
Car is being commanded to go on Fire Phase 1 recall via the main
keyswitch.
Car is commanded to exit Fire Phase 1 recall via the main
keyswitch.
When active, prevents the elevator from going to the recall floor
on fire recall. Used during prison operation.
In car Fire Phase 2 cancel keyswitch is ON. The car will cancel its
current destination and not take calls until the input is
deactivated.
In car Fire Phase 2 keyswitch is in the HOLD position.
In car Fire Phase 2 keyswitch is in the OFF position.
In car Fire Phase 2 keyswitch is in the ON position.
Car is being commanded to go on Fire Phase 1 recall via a remote
keyswitch. Only checked when programmed.
Seismic activity detected, puts car on Seismic Mode of operation.
Alternate recall floor smoke detector indicating fire is detected.
Hoistway smoke sensor indicating fire is detected.
Secondary hoistway smoke sensor indicating fire is detected. Used
for a jobsite where the group is split between two machine
rooms.
Main recall floor smoke detector indicating fire is detected.
Machine room smoke detector indicating fire is detected.
Secondary machine room smoke detector indicating fire is
detected. Used for a jobsite where the group is split between two
machine rooms.
Pit smoke sensor indicating fire is detected. Not checked if not
programmed
Table 36: Description of Front Doors Inputs
Indicates that the manual hall doors for the bottom floor front
opening are closed.
Door close button, requests that the front door closes