27.13.6 Default Factory
The user has the option to restore original factory settings.
The following procedure describes how to select default factory.
Navigate to MAIN MENU | SETUP | MISCELLANEOUS. See Figure 57.
From the MISCELLANEOUS menu, scroll and select Default. Figure 409.
From the DEFAULT menu, scroll and select Default Factory.
Figure 410: DEFAULT Menu – Default Factory
From the DEFAULT FACTORY? menu, select if restoring original factory settings.
Figure 422: DEFAULT FACTORY? Menu
From the DEFAULT FACTORY? menu, select Yes to default factory.
NOTE: If not defaulting factory, select NO to back out.
The system automatically defaults all parameters. See Figure 412.
When the system has completed defaulting all parameters, the DEFAULTING
PARAMETERS menu displays PARAMETERS DEFAULTED. See Figure 413.
27.13.7 Default FRAM
When Default FRAM is set to On, the FRAM chip automatically resets. This in turn clears the
fault and alarm logs, latched faults, emergency bits and run counters.
The following procedure describes how to default FRAM.
Navigate to MAIN MENU | SETUP | MISCELLANEOUS. See Figure 57.
From the MISCELLANEOUS menu, scroll and select Default. Figure 409.
From the DEFAULT menu, scroll and select Default FRAM.
Figure 423: DEFAULT Menu – Default FRAM