Hydro:Evolved User Manual
Page 174 © 2022 Smartrise Engineering, Inc. All Rights Reserved October 2022
A. Acceleration Rate - Rate at which the car accelerates before reaching maximum speed.
B. High Contract Speed - The maximum speed the car will achieve based on the contract
speed setting and the high valve setting.
C. NTS Buffer Distance: The distance added to the slowdown distance to cut off the high
valves.
D. Deceleration Rate - Rate at which the car decelerates after it reaches maximum speed.
E. Leveling Time - The duration the car moves during level speed before reaching the
destination.
F. Destination Offset - The distance from the destination position that the car will cut its
leveling valve when moving on a non-releveling run/correction run.
G. Slowdown Distance - Sets the distance from its destination where the car must cut its
high-speed valves when moving at a speed above the speed threshold.
H. TSRD Distance - The safe distance from the top and bottom floor level for a car to stop
before it hits the buffer. If the car is traveling more than 50 fpm within this distance, a
TSRD fault occurs and the car performs an emergency stop.
Place the car in Normal Operation. Prior to learning the hoistway verify the number of floors
and openings are correct. Learning the hoistway allows for learning the positioning of all floors.
18.4.1 Level Maximum Run Distance
Set the maximum run distance where level valve speed run is allowed. Longer runs outside of
door zones may start with a higher speed valve. When set to zero, a short distance run will start
with the higher valve and have a high likelihood of overshooting the destination.
The following procedure describes how to set the level maximum run distance.
Navigate to MAIN MENU | SETUP | HYDRO. See Figure 60.
From the HYDRO SETUP menu, scroll and select Level Maximum Run Distance.
Figure 304: HYDRO SETUP Menu Level Maximum Run Distance
From LEVEL MAXIMUM RUN DISTANCE menu, enter the maximum run distance.

Table of Contents

Other manuals for Smartrise HYDRO:EVOLVED

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Smartrise HYDRO:EVOLVED and is the answer not in the manual?

Smartrise HYDRO:EVOLVED Specifications

General IconGeneral
BrandSmartrise
ModelHYDRO:EVOLVED
CategoryController
LanguageEnglish

Related product manuals