Hydro:Evolved User Manual
Page 268 © 2022 Smartrise Engineering, Inc. All Rights Reserved October 2022
From the FLASH FIRE HAT menu, scroll and select ON. See Figure 476.
Scroll right and press Save.
31.3.9.3.3 Shunt Trip
A shunt output is designed to trip a breaker shutting off the main power to the controller in
case of a fire in the machine room.
The following procedure describes how to set up shunt trip when the alternate Machine room
smoke is triggered.
Navigate to MAIN MENU | SETUP | FIRE. See Figure 56.
From the FIRE SERVICE menu, scroll and select Alt. Machine Room. See Figure 498.
From the ALT MACHINE ROOM menu, scroll and select MR2 Smoke. See Figure 505.
From the MR 2 SMOKE menu, scroll and select Shunt Trip.
Figure 508: MR 2 SMOKE Menu – Shunt Trip
From the SHUNT ON RECALL menu, scroll and select ON. See Figure 478.
Scroll right and press Save.
31.3.10 Advanced Config
Advanced configuration is a simple way to configure specific fire parameters within the system.
For a description of each parameter, see the Hydro:Evolved Parameter List.
The following is a list of the specific parameters that can be configured.
• RESET TO EXIT PHASE 1
• DIS RSTCTR ON PHASE 2
• PHASE 2 SWING REOPEN DISABLED
• EXIT PHASE 2 ONLY AT RECALL FLOOR
• IGNORE LOCKS JUMPED ON PHASE 2
• FIRE STOP SWITCH KILLS DOOR OPERATOR
• DOL TO EXIT PHASE 2
• EXIT PHASE 1 AT MAIN RECALL ONLY
• OK TO STOP OUTSIDE DOOR ZONE
• ALLOW RESET WITH ACTIVE SMOKE
• HAT FLASH IGNORE ORDER
• MOMEMNTARY DOOR CLOSE BUTTON
• FLASH LOBBY FIRE LAMP
• REMOTE AND MAIN TO OVERRIDE SMOKE
• ENABLE PHE ON PH2